Workplace Safety

Fire Extinguisher Inspection Requirements UK: The Law, Checks and Servicing

Published 2026-11-11 · Worker Library editorial team

How we checked this guideRules quoted here (Regulatory Reform (Fire Safety) Order 2005, art. 17, Management of Health and Safety at Work Regulations 1999, reg. 5) were checked against the official text on legislation.gov.uk on 2026-10-21. This guide is general information, not legal advice.

Fire extinguisher inspection requirements in the UK rest on one short legal duty in England and Wales. The Regulatory Reform (Fire Safety) Order 2005 asks the responsible person to keep fire equipment under a suitable system of maintenance. This guide explains what that means, who it falls on, how monthly checks and servicing fit in, and how to keep a log that shows the system works.

Key takeaways
  • In England and Wales, fire extinguishers must be under a suitable system of maintenance and kept in efficient working order.
  • The duty falls on the responsible person for the premises; Scotland and Northern Ireland have their own fire safety law.
  • The Order sets no interval; monthly visual checks and an annual service to BS 5306-3 are common practice.
  • A written log is the simplest way to show the system of maintenance is working.
Free Excel templateFire Extinguisher Inspection Log

Free fire extinguisher inspection log in Excel: a register of every extinguisher with the annual maintenance date, and a monthly visual inspection log sheet.

Get the template

Fire extinguisher inspection requirements in the UK are often described as if the law set monthly checks and an annual service. In England and Wales the legal duty is shorter than that: article 17 of the Regulatory Reform (Fire Safety) Order 2005 says fire safety equipment must be subject to a suitable system of maintenance and kept in efficient working order and good repair. The intervals most businesses follow come from common practice and a British Standard, not from the Order. This guide separates the two, then shows how to keep a log.

The Order applies in England and Wales. Scotland and Northern Ireland have their own fire safety law; check the rules that apply there. This is general information, not legal advice. For the US rules, see the fire extinguisher inspection requirements guide.

Fire extinguisher inspection requirements in the UK come from article 17 of the Regulatory Reform (Fire Safety) Order 2005. Where necessary to safeguard the safety of relevant persons, the responsible person must ensure that the premises and any facilities, equipment and devices provided under the Order are subject to a suitable system of maintenance and are maintained in an efficient state, in efficient working order and in good repair.

Portable fire extinguishers are equipment provided for fire safety, so they fall within that duty. The same article reaches equipment provided under other laws, but only where it is provided in connection with general fire precautions (article 17(6)).

Three things the article does not say:

  • It does not set a monthly, six-monthly or annual interval.
  • It does not name a standard.
  • It does not prescribe a form or a retention period for records.

Those gaps are filled by what is "suitable" for the premises. In practice that means following the manufacturer's instructions and a recognised servicing standard, and being able to show it.

Who meets fire extinguisher inspection requirements in the UK

Fire extinguisher inspection requirements in the UK fall on the responsible person. The Order defines who that is; in a workplace it is usually the employer, and in other premises it is generally the person in control of them. Check the definition in the Order for your premises, because the duty in article 17 sits with that person.

Shared buildings need extra thought. Under article 17(2) to (5):

  • Where premises form part of a building, the responsible person may make arrangements with the occupier of other premises in the building to make sure the maintenance duty is met.
  • That applies even if the other premises are not covered by the Order.
  • The occupier of the other premises must co-operate with the responsible person.
  • Where the occupier is not the owner, the references to the occupier cover both.

In a multi-let office block, for example, the landlord may maintain extinguishers on common stairs while each tenant maintains its own. Write down who does what, so no extinguisher falls between two parties.

Fire extinguisher inspection requirements UK: how often

Fire extinguisher inspection requirements in the UK do not include a fixed interval in the Order. The law asks for a suitable system of maintenance; the usual pattern of monthly checks and an annual service comes from common practice and from BS 5306-3, which is commonly referenced for servicing portable extinguishers. A British Standard is not law, but following one is a common way to show a system is suitable.

CheckCommon intervalWho usually does itRecord
Visual checkMonthly, or more often in high-risk areas (common practice)A trained member of staffMonthly log with initials
Basic serviceAnnually (common practice, BS 5306-3 commonly referenced)Service company or competent technicianService label on the extinguisher, service report, register
Extended service or overhaulAt intervals set by type, per the standard and manufacturerService companyService report, register
After use, damage or tamperingEach timeService company for recharge or replacementRegister entry
Legal dutySuitable system of maintenance (art. 17)Responsible personNot prescribed

Your fire risk assessment is the place to set and justify the intervals for your building. Busy, dirty or exposed locations, such as loading bays or plant rooms, usually justify more frequent checks.

What a monthly fire extinguisher check covers in the UK

Fire extinguisher inspection requirements in the UK are met day to day by a short visual check. A monthly check takes a minute per extinguisher and catches the faults that make an extinguisher useless in a fire: missing, blocked, discharged or tampered with.

Common items:

  • The extinguisher is in its place, mounted or on a stand, and easy to see and reach
  • The pressure gauge, where fitted, reads in the operable range
  • The safety pin and tamper seal are intact
  • There is no visible damage, corrosion or leakage, and the hose and nozzle are clear
  • The service label is present and the last service is within its interval
  • Signs and operating instructions are readable

The person doing the check does not need to be a technician. They need to know what a good extinguisher looks like and who to tell when one is not.

Fire extinguisher servicing in the UK

Fire extinguisher inspection requirements in the UK are completed by periodic servicing. Servicing goes further than a visual check: the technician weighs, examines and, at set intervals, discharges or overhauls the extinguisher. The Order does not say who must service extinguishers, but a suitable system of maintenance points to someone with the training and equipment to do it, which in practice is usually a specialist service company.

What to agree with the service company:

  • Which extinguishers they service, by location or number
  • When each visit is due, and how they will remind you
  • What they leave behind: a label on each extinguisher and a written report
  • How they report extinguishers that are condemned or need replacing

Keep the service reports with your log. If the company finds an extinguisher that is the wrong type for the risk, such as water near electrical equipment, deal with it through the fire risk assessment.

Free Excel templateFire Extinguisher Inspection Log

Free fire extinguisher inspection log in Excel: a register of every extinguisher with the annual maintenance date, and a monthly visual inspection log sheet.

Get the template

Fire extinguisher inspection requirements UK: when a defect is found

Fire extinguisher inspection requirements in the UK turn on keeping equipment in efficient working order. An extinguisher that has been discharged, has a gauge out of range, a broken seal or visible damage is not in efficient working order, so it should be replaced or sent for service straight away.

A simple process:

  1. Take the extinguisher out of service and put a temporary replacement in its place if one is available.
  2. Record the defect, the date and who was told.
  3. Arrange recharge, repair or replacement through the service company.
  4. Record the action and the date the extinguisher was back in place.

Extinguishers used on a small fire must be recharged or replaced even if they look fine afterwards.

Fire extinguisher inspection requirements UK: records

The record side of fire extinguisher inspection requirements in the UK is not set out in article 17, which does not prescribe a form or a retention period. A written log is still the clearest evidence that a suitable system of maintenance exists and is working. It is also the first thing to hand over if a fire safety officer asks how equipment is maintained.

For workplaces, regulation 5 of the Management of Health and Safety at Work Regulations 1999 asks employers to make arrangements for the effective planning, organisation, control, monitoring and review of preventive and protective measures, and with five or more employees to record those arrangements. An extinguisher log fits naturally into those records.

What a useful log shows:

  • A register of every extinguisher: number, location, type and size, and service history
  • Monthly check results, with the date and initials
  • Service visits and reports
  • Defects, actions and dates

Many businesses keep logs for several years so trends and repeat problems are visible. That is a choice, not a rule in article 17.

Keeping the log with the template

Fire extinguisher inspection requirements in the UK are easiest to show with one file per building. The Fire Extinguisher Inspection Log has two sheets. It records your monthly checks and the service dates; the service report itself comes from the company that services the extinguishers.

What the file holds:

  • Extinguisher Register: one row per extinguisher, with location, type and size, manufacture year, last recharge, annual maintenance date, next due date (calculated 12 months ahead), service company, condition, gauge and action
  • Monthly Inspection Log: one line per extinguisher per check, with 5 checks (in place and visible, gauge, pin and seal, damage and hose, tag), the result, the action taken, the next due date and initials
  • 24 register rows and 30 log rows per sheet, with filled-in samples

The template was built with US defaults. Rename the "hydro test or internal maintenance due" column to match what your service company records, such as extended service or overhaul due, and set dates to day/month/year if you prefer. For other fire and building checks, the Facility Inspection Checklist and the Workplace Safety Inspection Checklist are useful alongside it.

Fire extinguisher inspection requirements UK FAQ

These are the questions about fire extinguisher inspection requirements in the UK that come up most often.

How often do fire extinguishers need to be serviced in the UK?

The Order does not set an interval. An annual service is common practice, with BS 5306-3 commonly referenced for servicing, plus monthly visual checks on site.

In England and Wales, the responsible person must keep fire safety equipment under a suitable system of maintenance and in efficient working order. Servicing is the usual way to do that.

Who can carry out monthly extinguisher checks?

A trained member of staff can do the monthly visual check. Servicing is usually done by a specialist service company.

Does the Fire Safety Order apply in Scotland?

No. The Order applies in England and Wales. Scotland and Northern Ireland have their own fire safety law; check the rules that apply there.

Check the current law at the link above and your service company's recommendations. This guide describes what the law asks for; it is not legal advice.

Free Excel templateFire Extinguisher Inspection Log

Free fire extinguisher inspection log in Excel: a register of every extinguisher with the annual maintenance date, and a monthly visual inspection log sheet.

Get the template